High output bedhead luminaire for hospital ward lighting. Class I electrical, Impact strength: IK08, IP44. Electronic, DALI-2 dimmable control gear. 2x DALI2 drivers. Luminaire made of aluminium, powder coated in white. Smooth radiused surfaces to facilitate cleaning and reduction of bacteria traps. Diffusers: polycarbonate. Independently controllable/dimmable direct and indirect light. Complete with 4000K LED for both direct and indirect component. Compliant with Cyanosis observation lighting requirements COI<3.3. Colour rendering Ra>90 (indirect), Ra>95 (direct).

Dimensions: 1004 x 83 x 135 mm
Luminaire input power: 79.2 W
Total luminous flux: 7860 lm
Luminaire efficacy: 105 lm/W
Weight: 4.2 kg

Mode selection
  • Lamp position:STD - standard
  • Light Source:LED
  • Luminaire luminous flux*:8355 lm
  • Luminaire efficacy*:105 lm/W
  • Colour Rendering Index min.:90
  • Correlated colour temperature*:4000 Kelvin
  • Chromaticity tolerance (initial MacAdam):3
  • Rated median useful life*:L80 50000 h at 25 °C
  • Ballast:1x HFI*
  • Luminaire input power*:79.2 W Power factor = 0.95
  • Dimming:Dali2Dim
  • LED
  • IK08
  • IP44
  • RCM
  • SC1 - Protection Class 1
  • Ta = -20 to +45

Photometry

Photometric configuration

CalcExpress

Use CalcExpress to quickly carry out quick online calculations of required indoor luminaire numbers for rectangular rooms. Enter the calculation parameters for your solution such as room dimensions, mounting height, height of the useful plane and required level of illuminance, and the site will instantly suggest a solution according to the light output ratio method.